Type EBU10-T
Description
The hybrid EBU10-T circuit breaker (Electronic Breaker Unit) has been particularly designed for the protection of AC UPS systems. The unit effectively ensures a stable supply and thus real power safety. The circuit breaker consists of an MCB and an add-on electronic circuitry, which takes over measuring and evaluation tasks. The product is available with the typical MCB ratings 4 A, 6 A, 10 A and 16 A with B and C characteristics and is directly operated at the output of the corresponding UPS. The device can be adjusted to the capabilities of the UPS used. In the event of a failure the circuit breaker will disconnect only the faulty path. A selective protection of UPS applications is therefore ensured. The electronic circuit breaker EBU10-T can be adjusted to the current rating of the UPS and the rated current of the load by means of a rotary switch.
Technical Data
operating voltage |
AC 230 V |
---|---|
Current ratings |
4 6 10 |
Number of poles |
1-pole 2-pole |
Load disconnection | with integrated circuit breaker |
Status indication | 1 LED green/orange/red: status/fault |
Terminal design |
PT-terminals screw terminals |
Mounting method | rail mounting |
Accessories
Order number | Description | |
---|---|---|
X22297750 |
label |
|
Y30850601 |
plug-on cap |
Applications
- (Steel industry)
- Automation
- Chemical, Oil & Gas
Downloads
Datasheet & Explanations
- Data sheet 1.9 MB
- Declaration of Conformity 130.3 KB
- Brochure 2.3 MB
- Instruction Manual 2.1 MB