Type: 3120-...-M...      Download
 
Dimensions
 
Internal connection diagrams
   
Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 60934). The addition of a magnetic tripping module to the type 3120 range extends the choices available to include single pole with thermal-magnetic protection; double pole switching with thermal-magnetic protection on one pole, thermal protection on the other; double pole switching with thermal-magnetic protection on one pole only. All are offered with rocker switch or push button control - two buttons for ON/OFF or one button press-to-reset only, in designs to suit one of three different panel cut-out sizes. Illumination is optional.
Approved to CBE standard EN 60934 (IEC 60934).
 
Voltage rating: 
  • AC 240 V (50/60 Hz)
  • DC 50 V
Current ratings: 
from 0.1 A to 16 A  
Number of poles: 
single pole 
double pole 
Mounting method: 
flange 
Terminal design: 
blade terminals 
screw terminals 
Actuation: 
manual release 
rocker 
Auxiliary contacts: 
without auxiliary contacts 
Water splash protection: 
with water splash protection 
without water splash protection 
Illumination: 
with illumination 
without illumination 
Typical life:
30,000 operations at 1 x IN, inductive, single pole
50,000 operations at 1 x IN, inductive, double pole
Interrupting capacity Icn:
0.1...2 A: 100 x IN
2.5...16 A: 250 A double pole or 150 A single pole
Approvals:
VDE, CSA, UL, CCC